JE-H(St)H Bd FE180 E30/E90
DownloadDatasheet PDF JE-H(St)H Bd FE180 E30/E90 Fire resistant cable APPLICATION As an installation cable for telecommunication purposes for fixed laying... read more
Description
JE-H(St)H Bd FE180 E30/E90
Fire resistant cable
APPLICATION
As an installation cable for telecommunication purposes for fixed laying in fire risk areas where particular protection against fire and fire damage is required for people and property and a system’s functional integ-rity must be maintained for 30 or 90 minutes. The cable has an insulation integrity of at least 180 minu-tes. The functional integrity is guaranteed under a test voltage of 110 V. The cable should be laid within buildings. When using a tube, the cables can also be laid outdoors or underground. During installation, the general test certificates issued by the cable and carrier system manufacturer must be observed. Also suitable
for use as a fire alarm cable with a red outer sheath.
Structure | |
Conductor | Copper conductor, bare, solid, based on DIN 4102, halogen-free dual insulation made from special mica tape and insulation material HI 2, cores stranded into pairs, 4 pairs stranded into bundles, bundles la- belled using colour-coded plastic tape covering, core wrapping made from plastic-laminated aluminium foil with drain wire. Wrapped with protective foil. |
Cores | Polymer compound insulation |
Drain wire | Copper drain wire |
Shield | Plastic-laminated metal foil with drain wire |
Outer sheath | Polymer compound |
Technical data | |
Nominal voltage | 225 V |
Test voltage | 800 V |
Loop resistance | 73.2 Ohm/gm |
Insulation resistance | 100 MOhm x km |
Operating capacity | 120 nF/km |
Operating temperature | -30°C bis +70°C |
Max. operating temperature | +70°C |
Capacitive coupling | For 100 m max. 300pF |
Min. installation temperature | -5°C |
Max. installation temperature | +50°C |
Flame retardancy | Halogen-free, flame-retardant HM2 sheath |
Min. bending radius | 15 x cable diameter |
Smoke density | HD 606 and IEC 601034-1, 601034-2 and BS 7622 part 1+2 |
Product description | Cu weight | Outer Ø (mm) | Weight (kg/km) | Fire load (kWh/m) |
JE-H(St)H Bd 2x2x0.8 Red FE180 E30/E90 | 25 | 7,5 | 74 | 0,19 |
JE-H(St)H Bd 4x2x0.8 Red FE180 E30/E90 | 45 | 10,9 | 127 | 0,33 |
JE-H(St)H Bd 8x2x0.8 Red FE180 E30/E90 | 85 | 14,5 | 232 | 0,56 |
JE-H(St)H Bd 12x2x0.8 Red FE180 E30/E90 | 126 | 17,1 | 318 | 0,77 |
JE-H(St)H Bd 16x2x0.8 Red FE180 E30/E90 | 166 | 19,6 | 430 | 1,08 |
JE-H(St)H Bd 20x2x0.8 Red FE180 E30/E90 | 206 | 21,5 | 514 | 1,25 |
JE-H(St)H Bd 32x2x0.8 Red FE180 E30/E90 | 327 | 27 | 730 | 1,89 |
JE-H(St)H Bd 40x2x0.8 Red FE180 E30/E90 | 407 | 28,9 | 962 | 002 |
JE-H(St)H Bd 52x2x0.8 Red FE180 E30/E90 | 527 | 33,2 | 0.001 | 003 |
JE-H(St)H Bd 2x2x0.8 Orange FE180 E30/E90 | 25 | 7,5 | 74 | 0,19 |
JE-H(St)H Bd 4x2x0.8 Orange FE180 E30/E90 | 45 | 10,9 | 127 | 0,33 |
JE-H(St)H Bd 8x2x0.8 Orange FE180 E30/E90 | 85 | 14,5 | 232 | 0,56 |
JE-H(St)H Bd 12x2x0.8 Orange FE180 E30/E90 | 126 | 17,1 | 318 | 0,77 |
JE-H(St)H Bd 16x2x0.8 Orange FE180 E30/E90 | 166 | 19,6 | 430 | 1,08 |
JE-H(St)H Bd 20x2x0.8 Orange FE180 E30/E90 | 206 | 21,5 | 514 | 1,25 |
JE-H(St)H Bd 32x2x0.8 Orange FE180 E30/E90 | 327 | 27 | 730 | 1,89 |
JE-H(St)H Bd 40x2x0.8 Orange FE180 E30/E90 | 407 | 29,8 | 962 | 002 |
JE-H(St)H Bd 52x2x0.8 Orange FE180 E30/E90 | 527 | 33,2 | 1200 | 003 |
SPECIAL FEATURES
Properties
Halogen free
Sheath colour